Q6Z0124A
Parameter
set 1
set 2
set 3
set 4
DTOC1:
IN>>> PSx
076 056
077 056
078 056
079 056
DTOC1:
IN>>> dynamic PSx
076 156
077 156
078 156
079 156
DTOC1:
tIN>>> PSx
076 062
077 062
078 062
079 062
DTOC1:
Gen.starting modePSx
076 066
077 066
078 066
079 066
DTOC1:
Block tim.st. IN PSx
076 067
077 067
078 067
079 067
Parameter
set 1
set 2
set 3
set 4
DTOC1:
IN> PSx
076 054
077 054
078 054
079 054
DTOC1:
IN> dynamic PSx
076 154
077 154
078 154
079 154
DTOC1:
tIN> PSx
076 060
077 060
078 060
079 060
DTOC1:
IN>> PSx
076 055
077 055
078 055
079 055
DTOC1:
IN>> dynamic PSx
076 155
077 155
078 155
079 155
DTOC1:
tIN>> PSx
076 061
077 061
078 061
079 061
DTOC1:
Block tim.st. IN PSx
[ * ]
0: Without
1: For single-ph. start
0
1
DTOC1:
Trip signal tIN>
[ 035 126 ]
MAIN:
Protection active
306 001
DTOC1:
Starting A
[ 035 104 ]
DTOC1:
Starting B
[ 035 105 ]
DTOC1:
Starting C
[ 035 106 ]
2: For multi-ph. start.
2
DTOC1:
IN> PSx
[ * ]
DTOC1:
IN> dynamic PSx
[ * ]
DTOC1:
tIN> PSx
[ * ]
DTOC1:
IN>> PSx
[ * ]
DTOC1:
IN>> dynamic PSx
[ * ]
DTOC1:
tIN>> PSx
[ * ]
DTOC1:
IN>>> PSx
[ * ]
DTOC1:
IN>>> dynamic PSx
[ * ]
DTOC1:
tIN>>> PSx
[ * ]
DTOC1:
tIN> elapsed
[ 035 117 ]
DTOC1:
Trip signal tIN>>
[ 035 130 ]
DTOC1:
tIN>> elapsed
[ 035 118 ]
DTOC1:
Starting IN>
[ 035 111 ]
DTOC1:
Trip signal tIN>>>
[ 035 131 ]
DTOC1:
tIN>>> elapsed
[ 035 119 ]
DTOC1:
Starting IN>>
[ 035 112 ]
DTOC1:
Starting IN>>>
[ 035 113 ]
DTOC1:
Starting N
[ 035 107 ]
DTOC1:
Gen.starting modePSx
[ * ]
1: With start. IN/Ineg
DTOC1:
Enabled
[ 035 102 ]
DTOC1:
Block. tIN> EXT
[ 035 123 ]
DTOC1:
Block. tIN>> EXT
[ 035 124 ]
IN,y
MAIN:
Dynam. param. active
[ 040 090 ]
DTOC1:
Block. tIN>>> EXT
[ 035 125 ]
0
c
t
c
c
0
c
t
c
c
0
c
t
c
c
Fig. 3-94: Residual current stages
3.22.5 General Starting
If the current exceeds one of the set thresholds of the phase current stages, a
general starting decision is issued. The user can select whether the starting of
3 Operation
P631
P631/EN M/R-11-C // P631-310-650 3-129