Parameter Address
Default Min Max Unit Logic Diagram
PC link
PC: Bay address
003 068
1 0 254 Fig. 3-5, (p. 3-9)
[spacer]
PC: Device address
003 069
1 0 255 Fig. 3-5, (p. 3-9)
[spacer]
Bay and device addresses are used to address the device in communication via
the PC interface. An identical setting must be selected for both addresses.
[spacer]
PC: Baud rate
003 081
115.2: 115.2 kBaud Baud Fig. 3-5, (p. 3-9)
[spacer]
Baud rate of the PC interface.
[spacer]
PC: Parity bit
003 181
1: Even Fig. 3-5, (p. 3-9)
[spacer]
Set the same parity that is set at the interface of the PC connected to the P631.
[spacer]
PC: Spontan. sig. enable
003 187
0: None Fig. 3-5, (p. 3-9)
[spacer]
Enable for the transmission of spontaneous signals via the PC interface.
[spacer]
PC: Select. spontan.sig.
003 189
060 000: MAIN: Without function Fig. 3-5, (p. 3-9)
[spacer]
Selection of spontaneous signals for transmission via the PC interface.
[spacer]
PC: Transm.enab.cycl.dat
003 084
0: Without Fig. 3-5, (p. 3-9)
[spacer]
Enable for the cyclic transmission of measured values via the PC interface.
[spacer]
PC: Cycl. data ILS tel.
003 185
060 000: MAIN: Without function Fig. 3-5, (p. 3-9)
[spacer]
Selection of the measured values that are transmitted in a user-defined
telegram via the PC interface.
[spacer]
PC: Delta V
003 055
3.0 0.0 15.0 %Vnom Fig. 3-5, (p. 3-9)
[spacer]
A measured voltage value is transmitted via the PC interface if it differs by the
set delta quantity from the last measured value transmitted.
[spacer]
PC: Delta I
003 056
3.0 0.0 15.0 %Inom Fig. 3-5, (p. 3-9)
[spacer]
A measured current value is transmitted via the PC interface if it differs by the
set delta quantity from the last measured value transmitted.
[spacer]
PC: IP address
111 004
192 0 255
7 Settings
P631
P631/EN M/R-11-C // P631-310-650 7-13