Par/Conf menu branch:
●
PC: Bay address
●
PC: Device address
●
PC: Baud rate
●
PC: Parity bit
●
COMM1: Function group COMM1
●
COMM1: General enable USER
●
COMM1: Name of manufacturer
●
COMM1: Line idle state
●
COMM1: Baud rate
●
COMM1: Parity bit
●
COMM1: Communicat. protocol
●
COMM1: Octet comm. address
●
COMM1: Octet address ASDU
●
COMM2: Function group COMM2
●
COMM2: General enable USER
●
COMM2: Name of manufacturer
●
COMM2: Line idle state
●
COMM2: Baud rate
●
COMM2: Parity bit
●
COMM2: Octet comm. address
●
COMM2: Octet address ASDU
Par/Func/Glob menu branch:
●
PC: Command blocking
●
PC: Sig./meas.val.block.
●
COMM1: Command block. USER
●
COMM1: Sig./meas.block.USER
●
COMM2: Command block. USER
●
COMM1: Sig./meas.block.USER
Instructions on these settings are given in Chapters “Settings” and “Information
and Control Functions”.
The settings given above apply to the IEC 60870-5-103 communication protocol. If
another protocol is being used for the communication interface, additional settings
may be necessary. See Chapter “Settings” for further details.
After the settings have been made, the following checks should be carried out
again before the blocking is cancelled:
●
Does the function assignment of the binary signal inputs agree with the
terminal connection diagram?
●
Has the correct operating mode been selected for the binary signal inputs?
●
Does the function assignment of the output relays agree with the terminal
connection diagram?
●
Has the correct operating mode been selected for the output relays?
●
Have all settings been made correctly?
P631
10 Commissioning
10-4 P631/EN M/R-11-C // P631-310-650