Parameter Address
[spacer]
SFMON: Error K 706
097 083
[spacer]
SFMON: Error K 901
097 094
[spacer]
SFMON: Error K 902
097 095
[spacer]
SFMON: Error K 903
097 096
[spacer]
SFMON: Error K 904
097 097
[spacer]
SFMON: Error K 905
097 098
[spacer]
SFMON: Error K 906
097 099
[spacer]
SFMON: Error K 907
097 100
[spacer]
SFMON: Error K 908
097 101
[spacer]
Output relay K xxx defective.
Device reaction: –
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: Undef. operat. code
093 010
[spacer]
Undefined operation code.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Abnormal termination
093 030
[spacer]
The application has been terminated in an unexpected way. If this error occurs
during a (re-)start of the device then this message is displayed and the device is
blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Bad arg. system call
093 031
[spacer]
Invalid parameter when calling a function of the operating system. If this error
occurs during a (re-)start of the device then this message is displayed and the
device is blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
P631
11 Troubleshooting
11-6 P631/EN M/R-11-C // P631-310-650