SFMON: Inval. SW vers.comm.
093 075
[spacer]
Incorrect or invalid communication software has been downloaded.
Device reaction: –
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
[spacer]
SFMON: Inval. Config. IEC
093 079
[spacer]
Invalid parameters in the IEC configuration.
Device reaction: –
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
[spacer]
SFMON: Invalid SW vers. Y
093 113
[spacer]
Incorrect or invalid software for analog I/O module Y has been downloaded.
Device reaction: –
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
[spacer]
SFMON: Time-out module Y
093 112
[spacer]
Watchdog is monitoring the periodic status signal of the analog I/O module Y. It
has detected an error.
Device reaction: –
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
[spacer]
SFMON: M.c.b. trip V
098 000
[spacer]
The line-side voltage transformer m.c.b. has tripped.
Device reaction: Blocking of the short-circuit direction determination.
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
[spacer]
SFMON: Meas. circ. I faulty
091 018
[spacer]
The measuring-circuit monitoring function has detected a fault in the current-
measuring circuits. (See functions MCMON and CTS, measuringcircuit monitoring
multiple signal.)
Device reaction: –
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
[spacer]
SFMON: Meas. c. I faulty, a
091 026