Version Changes
LED, MAIN, ... The English designation text of the following data point
has been changed, but functionality remains
unchanged. The old designation is shown on the left
and the new designation on the right-hand side.
CTS: Reset latching EXT → CTS: Reset latch.
EXT
P631
‑308
‑407/408
‑622-724
Release: 2012-02-01
Hardware
No changes.
Diagram
No changes.
Software
IEC
Bug fixing:
●
If clients did connect to the device immediately
after completion of Ethernet communication
module startup, this could lead to the temporary
erroneous reporting of default values for the
external device status (DEVxx) and of the single-
pole signals (SIG_1).
●
If single-pole signals of function group SIG_1 were
active during device startup, this could lead to an
aborted initialization of the Ethernet
communication module.
●
During the process of connection with clients that
use the “IntegrityPeriod” option, sporadically the
MMS communication of the Ethernet
communication module would crash without an
internal monitoring response to re-establish the
functionality. (GOOSE messaging and other
communication tasks were not affected.)
●
Reports of events could get lost if too many state
changes occurred in a short period of time,
especially during secondary injection testing.
GOOSE The GOOSE Time Allowed to Live (TAL) supervision is
enhanced with respect to simultaneous state changes
of multiple GOOSE messages.
PC, COMM2
Bug fixing:
●
If clients did connect to the device immediately
after startup of the Ethernet communication
module, the initialization of the second internal
communication interface could remain
incomplete. As a consequence, access by the
operating program via the COMM2 interface or by
tunneling was not possible in this case.
A5 P631 Version History
P631
P631/EN M/R-11-C // P631-310-650 A5-23