12 - 11
12 ERROR CODE LISTS
Error
code
Details
code
Error factor
Error Processing Corrective Action
Name Description
16320 —
Operation (/)
execution error
The divisor is 0.
The block processing
on executing is
stopped and the next
block is executed.
Correct the program so that the divisor is
other than 0.
16321 —
Remainder (%)
execution error
16322 —
Device set (SET)
execution error
• The device No. which indirectly specifies
(D) is illegal.
• (D) is a device which is write-disabled.
• Correct the program so that the device No.
which indirectly specifies (D) is proper.
• Correct the program to set a write-enabled
device at (D).
16333 —
Device reset (RST)
execution error
16334 —
Device set (SET=)
execution error
16335 —
Device reset (RST=)
execution error
16336 —
Device output (DOUT)
execution error
16337 —
Device input (DIN)
execution error
The device No. which indirectly specifies (D)
is illegal.
Correct the program so that the device No.
which indirectly specifies (D) is proper.
16338 —
Bit device output
(OUT=) execution
error
16368 —
Direct specification 16
bit Multiple CPU area
device for CPU No.1
(U3E0\G10000 to)
read error
Multiple CPU area device number is outside
the range that set by the parameter.
Correct the program so that Multiple CPU
area device number is within the range set
in the parameter.
16369 —
Direct specification 32
bit Multiple CPU area
device for CPU No.1
(U3E0\G10000 to)
read error
16370 —
Direct specification 64
bit Multiple CPU area
device for CPU No.1
(U3E0\G10000 to)
read error
16371 —
Direct specification 16
bit Multiple CPU area
device for CPU No.2
(U3E1\G10000 to)
read error
16372 —
Direct specification 32
bit Multiple CPU area
device for CPU No.2
(U3E1\G10000 to)
read error
16373 —
Direct specification 64
bit Multiple CPU area
device for CPU No.2
(U3E1\G10000 to)
read error
16374 —
Direct specification 16
bit Multiple CPU area
device for CPU No.3
(U3E2\G10000 to)
read error
16375 —
Direct specification 32
bit Multiple CPU area
device for CPU No.3
(U3E2\G10000 to)
read error