12 - 20
12 ERROR CODE LISTS
Error
code
Details
code
Error factor
Error Processing Corrective Action
Name Description
16467
Indirect specified 64-
bit data register
(D(n)F) read error
The indirectly specified device No. is outside
the range or an odd number.
The block processing
in execution is
stopped and the next
block is executed.
Correct the program so that the indirectly
specified device No. is proper.
16468
Indirect specified 16-
bit link register (W(n))
read error
The indirectly specified device No. is outside
the range.
16469
Indirect specified 32-
bit link register
(W(n)L) read error
The indirectly specified device No. is outside
the range or an odd number.
16470
Indirect specified 64-
bit link register
(W(n):F) read error
16475
Indirect specified
SM(SM(n)) read error
The indirectly specified device No. is outside
the range.
16482
Direct specified
Multiple CPU area
device bit specified for
CPU No.1
(U3E0\G10000.0 to)
read error
Multiple CPU area device number is outside
the range set in the parameter.
Correct the program so that Multiple CPU
area device number is within the range set in
the parameter.
16483
Direct specified
Multiple CPU area
device bit specified for
CPU No.2
(U3E1\G10000.0 to)
read error
Multiple CPU area device number is outside
the range set in the parameter.
16484
Direct specified
Multiple CPU area
device bit specified for
CPU No.3
(U3E2\G10000.0 to)
read error
16485
Direct specified
Multiple CPU area
device bit specified for
CPU No.4
(U3E3\G10000.0 to)
read error
16486
Indirect specified input
relay (X(n)) read error
The indirectly specified device No. is outside
the range.
Correct the program so that the indirectly
specified device No. is proper.
16487
Indirect specified
output relay (Y(n))
read error
16488
Indirect specified
internal relay (M(n))
read error
16489
Indirect specified link
relay (B(n)) read error
16490
Annunciator (F(n))
read error
16516
Indirect specified 16-
bit batch input relay
(X(n)) read error
The indirectly specified device No. is
outside the range or is not a multiple of 16.
16517
Indirect specified 32-
bit batch input relay
(X(n)) read error
16518
Indirect specified 16-
bit batch output relay
(Y(n)) read error
16519
Indirect specified 32-
bit batch output relay
(Y(n)) read error