3 MAJOR POSITIONING CONTROL
3.1 Outline of Major Positioning Controls
51
3
Operation patterns of major positioning controls
In "major positioning control" (high-level positioning control), "[Da.1] Operation pattern" can be set to designate whether to
continue executing positioning data after the started positioning data. The "operation pattern" includes the following 3 types.
Independent positioning control (Positioning complete)
This control is set when executing only one designated data item of positioning. If a dwell time is designated, the positioning
completes after the designated time elapses.
This data (operation pattern [00] data) becomes the end of block data when carrying out block positioning. (The positioning
stops after this data is executed.)
Positioning control Operation pattern
Positioning complete Independent positioning control (operation pattern: 00)
Positioning continue Continuous positioning control (operation pattern: 01)
Continuous path control (operation pattern: 11)
[RD77MS4 operation example]
Positioning start signal [Y10, Y11, Y12, Y13]
OFF
ON
Dwell time
Start complete signal ([Md.31] Status: b14)
OFF
ON
BUSY signal [X10, X11, X12, X13]
OFF
ON
Positioning complete signal
([Md.31] Status: b15)
OFF
ON
Positioning complete (00)