3.5.19 AT differential gap (buffer memory address 46, 78: Un\G46, Un\G78)
(1) Set the waiting time needed for next switching of output ON/OFF status from the
previous switching at auto tuning.
(2) The setting range is 0 to 10000 (0.00 to 100.00s).
(3) The target of setting value for standard mode is 10 (0.1s), for fast response
mode is 1 (0.01s).
Measured value
Set value (SV)
Output
Measured
value (PV)
Time
AT difference gap
3.5.20 AT additional lag (buffer memory address 47, 79: Un\G47, Un\G79)
(1) Set the waiting time for switching the output ON/OFF status after the measured
value (PV) has passed the set value (SV) at auto tuning.
(2) The setting range is 0 to 1000 (0.00 to 10.00s).
(3) The target of setting value for standard mode is 10 (0.1s), for fast response
mode is 1 (0.01s).
Measured value
Set value (SV)
Output
Time
AT additional lag
Measured value
(PV)

Table of Contents

Other manuals for Mitsubishi Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q Series and is the answer not in the manual?

Mitsubishi Q Series Specifications

General IconGeneral
I/O PointsUp to 4096 points
CommunicationEthernet, RS-232, RS-485
I/O ModulesDigital, Analog, Specialized
Programming LanguageFunction Block Diagram, Structured Text
Power Supply24V DC, 100-240V AC
Operating Temperature0°C to 55°C
Shock Resistance147 m/s2 acceleration, 3 times in each of X, Y, and Z directions
Program CapacityUp to 252K steps