6 - 5 6 - 5
MELSEC-Q
6 PROGRAMMING
6.2.1 Program example using the utility package
(1) Operation of utility package
(a) Initial setting (Refer to Section 5.4)
<When cascade control is not executed>
CH1 Input Range........................................................"0"
CH2 Unused Channel Setting...................................."Not Used"
[Limiter setting]
CH1 Upper Setting Limiter ........................................."2000"
CH1 Lower Setting Limiter ........................................."0"
[Alert function setting]
CH1 Alert 1 Mode Setting .........................................."UprLmt Input"
CH1 Alert Set Value 1 ................................................"1800"
[Normal control setting]
CH1 Set Value (SV) setting ......................................."800"
[Program control setting]
CH1 Execution Pattern..............................................."Program Pattern 1"
CH1 Time Scale ........................................................."1s"
CH1 Program Pattern 1
Final Segment ...................................................."4"
Segment 1 Set Value (SV) setting....................."1500"
Segment 1 Executing Time ..............................."200"
Segment 1 Zone PID data No. ........................."2"
Segment 2 Set Value (SV) setting....................."1500"
Segment 2 Executing Time ..............................."100"
Segment 2 Zone PID data No. .........................."2"
Segment 3 Set Value (SV) setting....................."500"
Segment 3 Executing Time ..............................."100"
Segment 3 Zone PID data No. .........................."1"
Segment 4 Set Value (SV) setting....................."500"
Segment 4 Executing Time ..............................."100"
Segment 4 Zone PID data No. .........................."1"
<When cascade control is executed>
CH1 Input Range........................................................"0"
CH2 Input Range........................................................"0"
CH1 Unused Channel Setting...................................."Used"
CH2 Unused Channel Setting...................................."Used"
[Limiter setting]
CH1 Upper Setting Limiter ........................................."2000"
CH1 Lower Setting Limiter ........................................."0"
CH2 Upper Setting Limiter ........................................."2000"
CH2 Lower Setting Limiter ........................................."0"
[Normal control setting]
CH1 Set value (SV) setting ........................................"1000"