3 - 23 3 - 23
MELSEC-Q
3 SPECIFICATIONS
(3) The Q62HLC allows four different alerts (alerts 1 to 4) to be selected and used
from among the alerts, wait alert and re-wait alert.
Set the alert modes used as alerts 1 to 4 at the following buffer memory
addresses:
Buffer memory addresses (Decimal)
Channel No.
Alert 1 Alert 2 Alert 3 Alert 4
1 192 193 194 195
2 208 209 210 211
(4) Set the alert set value, alert dead band setting and alert delay count at the
following buffer memory addresses:
Buffer memory addresses (Decimal)
Channel No.
Alert set value Alert dead band setting Alert delay count
1 38 to 41
2 70 to 73
164 165
3.2.11 Control output setting at CPU stop error occurrence function
(1) You can set the Q62HLC control output (HOLD/CLEAR) to be provided when
the programmable controller CPU has generated a stop error.
(2) To make this setting, use the intelligent function module switch setting on GX
Developer.
• CLEAR : Stops the PID control, temperature judgement and alert judgement
functions and turns off external outputs.
• HOLD : Continues the control status prior to a programmable controller CPU
stop. For example, when PID control was exercised before a
programmable controller CPU stop, PID control is continued if the
programmable controller CPU stops.
Refer to Section 4.5 for details of the setting method.