4 - 5 4 - 5
MELSEC-Q
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
4.4 Wiring
This section provides wiring instructions and module connection examples.
4.4.1 Wiring precautions
External wiring must be noise-resistant as one of the conditions to fully exhibit the
Q62HLC functions and configure a highly reliably system.
The instructions given below should be followed in wiring.
(1) Use separate cables with the AC control circuit and Q62HLC's external I/O signals
to avoid the influence of AC side surges and induction.
(2) Do not run the cables close to, or bundle them with, the main circuit and high-
voltage cables and the load cables from other than the programmable controller.
Always keep thermocouple/micro voltage signal line at least 100mm(3.94inch)
away from the main circuit cables and AC control circuit.
Fully keep them away from high-voltage cables and circuits which include high
frequencies, e.g. inverter load's main circuit.
Failure to do so will make the cables susceptible to noise, surges and induction.
(3) Ground the shield wires or shield cables to FG of the programmable controller.
Note that it may be better to establish a ground on the external side depending on
the external noise conditions.
(4) When you want the equipment to conform with the EMC Directive/Low Voltage
Directive, refer to "Conformance with the EMC Directive and Low Voltage
Directive" in this manual and carry out wiring.

Table of Contents

Other manuals for Mitsubishi Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q Series and is the answer not in the manual?

Mitsubishi Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelQ Series
CategoryControl Unit
LanguageEnglish

Related product manuals