EasyManua.ls Logo

Munters Element - Page 68

Munters Element
83 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© Munters AB, 2018 68
o
Target Diff: When the temperature rises to the Target Temperature plus this differential,
cooling starts.
o
To Humidity: Cooling only operates when the humidity is less than this level. Default: 0.
Setting this parameter to 0 or 100 disables the sensor input to this function.
If the sensor sends invalid readings, Element will ignore the Humidity settings.
In a situation where there are multiple data lines for a single day and the
humidity level rises to the temperature setting (plus differential), cooling stops
entirely. It does not roll back to the previous setting.
o
On/Off: Set timing values (in seconds) for the On/Off cycle. Default: 0
o
Cooling: Select cooling device. Default: no cooling device selected
o
Start/End Time: Set the cooling operation time. Default: 00:00 23:59
NOTE Setting the start/end times to 00:00 to 00:00 disables the function.
3. If required, go to Control > Cooling > Set.
4. Define the following parameters:
o
From Level: Define the minimum ventilation level at which cooling can begin: Default: 1
o
Temperature Band: When the temperature reaches the target temperature plus this
differential minus the temperature band, cooling stops. Range: 0.2 20.0. Default:
1.1 (see Figure 33)
o
Humidity Band (%): Hysteresis band for Humidity Treatment. Range: 1 20%:
Default: 2%
Figure 33: Cooling Temperature On Off

Table of Contents

Related product manuals