© Munters AB, 2020 104
Maximum Additional Ventilation: Define the maximum ventilation
adjustment to cycle times or speed to variable speed fans. Range: 1 –
100%. Default: 20%
Inside T° to Stop Treatment (Diff Below Target): Define the difference
below the target temperature at which additional ventilation
treatment ceases. Range: 0 - 50°. Default 2°.
o
Treatment by Heat:
Maximum Additional Heat (%): The maximum increase in heat (max
compensation). Either the cycle time or heat intensity in variable
heaters increases. Range: 1% to 100%
Outside T⁰ To Operate By Heaters (Diff Below Target): Below this
difference from the target temperature the controller automatically
adjusts the heat output to compensate the air quality. Range -40°to
+90°
Inside T° to Stop Treatment (Diff Above Target): Above this difference
from the target temperature the controller stops this heat treatment.
Range: 0 - 50°. Default: 2°.
o
RH Shutoff Differential: (%): Below this level, humidity treatment ceases.
Range: 0% to 10%
o
High RH Alarm Threshold (%): Trio sends an alarm when the humidity level
rises above this level. Range: 0% to 100%
o
Co2 Shutoff Differential: (ppm): When CO2 levels are below the target level
by this amount, all CO2 treatment stops. Range: 0 to 500 ppm
o
High Co2 Alarm threshold (ppm): Trio sends an alarm when the CO2 level
rises above this level. Range: 0 to 5000 ppm
o
NH3 Shutoff Differential: (ppm): When ammonia levels are below the target
level by this amount, all ammonia treatment stop. Range:0 ppm to 10 ppm
o
High NH3 Alarm threshold (ppm): Trio sends an alarm when the ammonia
level rises above this level. Range: 0 to 100 ppm