© Munters AB, 2020 40
7.2.2.1
Minimum Ventilation Cycle
1. Go to Go to Climate > Ventilation > Settings.
2. Define:
o
Total Cycle Time (sec): Define the minimum ventilation cycle time. Range: 60
– 999 seconds.
o
Min Cycle Off Time (sec.): When using cycle time, Trio automatically adjusts
the ON time set in the main screen. This parameter defines the minimum
cycle off time. Range: 0 – 600 seconds.
3. Go to System > Control Strategy > Ventilation .
4. Enable Fan Cycle (Basic).
5. Go to Climate > Ventilation. The (Fan) On time appears on the screen.