© Munters AB, 2020 37
7.2
Basic Ventilation
Basic Level Ventilation defines the amount of air to be supplied at each level of minimum
ventilation level. As the temperature increases, minimum ventilation increases the amount
of air supplied to maintain the temperature as close to the target temperature as possible
•
Fans controlled by relays are on/off. When they are on, they run at maximum
speed. Variable fans’ speed can be controlled, according to needs.
•
As you configure the levels, make sure that ventilation increases as the levels
increase. Trio displays each levels fan output. When using on/off fans (fans
controlled by relays) increasing the number of fans increases the ventilation.
When using analog fans, the user defines the fans’ maximum output; this output
must be taken into account along with the number of fans.
•
Defining Basic Ventilation
•
Fan Options
•
Inlet and Curtain Ventilation
7.2.1
D
EFINING
B
ASIC
V
ENTILATION
In this configuration, Trio raises the minimum ventilation from 10% at Level One to 100% at
Level 10.
In Devices and Sensors map relays and analog output ports to fans, inlets, and stir
fans as required. Only mapped devices show up in the following screens.
1. Go to Climate > Ventilation.
NOTE At this point, fans do not appear.
2. Click .