Alarms
•
Defining the Alarm Parameters
•
Viewing the Alarms
•
Defining the Auxiliary Alarms
•
Sending a General Alarm
16.1
Defining the Alarm Parameters
•
Alarm Definitions
•
Alarm Test
16.1.1
A
LARM
D
EFINITIONS
1. Go to System > Control Strategy > Alarms .
NOTE Water Overflow, Water Shortage, and Potentiometer only appear if these devices
are mapped. Refer to Devices and Sensors.
2. Click
.
3. Define:
o
Alarm delay: After detecting that a parameter has gone above or below its
specs, Trio waits this amount of time before sending an alarm. This prevents
sending alarms for short deviations. Range: 0 – 999 seconds.
o
Alarm Reminder: Trio will resend an alarm after this amount of time if the
alarm is not acknowledged. Range: 0 – 999 minutes.