Defining the Tunnel Ventilation
Defining the Tunnel Ventilation Settings
Tunnel Doors
Defining the Wind Chill Factor
7.4.1
D
EFINING THE
T
UNNEL
V
ENTILATION
P
ARAMETERS
1. Go to System > Control Strategy > Ventilation .
2. Under Ventilation:
a. Enable Tunnel.
b. Select the tunnel operation mode (refer to Inlet and Curtain Ventilation, page
46 for details on this parameter).
3. Go to Climate > Temperature Curve.
4. For each day, define the Tunnel temperature. This parameter defines the
temperature at which Tunnel Mode begins to operate.
5. Go to Climate > Ventilation and click the Tunnel Tab.