© Munters AB, 2020 22
4.2
Configuring the Temperature Curve
•
Defining the Temperature Curve
•
Defining Temperature Curve Settings
4.2.1
D
EFINING THE
T
EMPERATURE
C
URVE
P
ARAMETERS
1. Go to Climate > Temperature Curve.
2. Configure up to 10 points in the curve.
3. Define:
o
Day: Define the growth day at which each temperature spec applies. Each
day must have a unique number. Range: 0 – 999.
o
Target: Target temperature is the required temperature for the bird house.
All ventilation calculations are based on this specification. Range -40⁰ to
+90⁰ C/-40⁰ to +194⁰ F.
o
Heat: This parameter is the set point at which the heaters are activated.
o
Cool: This parameter is the set point at which cooling devices are activated.
When the target temperature changes, this number changes accordingly.
Range: Target temperature to +90⁰ C.
NOTE Heat and Cool appear if a heater and cooler are defined in Devices and Sensors.
o
Tunnel: This parameter is the set point at which tunnel ventilation begins.
When the target temperature changes, this number changes accordingly.
Range: Target temperature to +90⁰ C/194⁰ F.
NOTE Zone Heat and Cool only appear if relays are defined as Zone Heaters or Cooler
(refer to the Installation Manual). Tunnel appears if Tunnel Ventilation is enabled in
Ventilation Settings (page 52).
o
Low/High Temperature Alarm: These parameters are differentials from the
target temperature at which Trio sends an alarm. Range:
Low Temp Alarm: -40°- Target
High Temp Alarm: Target - 90°C/194⁰ F
4. Click to view the curve history.