6.2
Defining Basic Ventilation
1. Go to System > Control Strategy > Ventilation .
2. Verify that Dynamic Minimum/Maximum and Min Ventilation are disabled.
3. Go to Climate > Min/Max Ventilation.
4. Click
.
5. Define:
o
Day: Set the growth day for the required min/max set points. Each day must
have a unique number. Add up to ten lines.
o
Min/Max Level: Define the minimum and maximum ventilation levels. Trio
will automatically adjust the ventilation as the temperature changes.
Extra/Tunnel Minimum Ventilation: As option when additional minimum ventilation is
required in hot climates, Extra and Tunnel Ventilation can provide minimum ventilation.
6. In System > Control Strategy > Ventilation , enable Extra Ventilation and/or
Tunnel (refer to Defining Extra Ventilation, page 50).
7. Go to Climate > Min. Max. Ventilation.
8. Place the cursor in Min Level or Max Level. The Basic/Extra/Tunnel icons appear.