NMC-PRO
USER GUIDE
Doc. Name: NMC-PRO ׀ User Guide Ver 3.05.03 Revision: 2.2 Page: 20
Crop Management Technologies
# Parameter Explanation Unit/Range Default
8.
Wind Influence
Define the conversion table that indicates the
influence of the wind speed level outside on the
ventilation temperature.
*See Wind Speed Influence below
0-50 m/sec 0
9.
Cool Down
Define the gradual cooling down time per 1
o
C
(approximately 2F). This is used to avoid fast
changes between periods.
*
For example: Setting this parameter to 15
minutes (00:15) means that it will take one hour
for the zone to cool down from 24°C to 20°C (15
minutes per 1°C).
hh:mm 00:15
10.
Heat up
Define the gradual heating time per 1
o
C
(approximately 2F). This is used to avoid fast
changes between periods.
*
For example: Setting this parameter to 15
minutes (00:15) means that it will take one hour
for the zone to heat up from 20°C to 24°C (15
minutes per 1°C).
hh:mm 00:15
Calculated / Status
11.
Calculated Top
Vent Temp.
Calculates the temperature for the opening of
the top vent corresponding with the settings
defined and taking into consideration the
influences.
0
o
to +100° C
12.
Calculated Side
Vent Temp.
Calculates the temperature for the opening of
the side vent corresponding with the settings
defined and taking into consideration the
influences.
0
o
to +100° C
13.
Vent Limitation
Vent function may be limited due to a higher
priority event.
Ex: If it is raining, then the vents will proceed to
the “RAIN” position, and the Vent Limitation will
display Rain.
1. Manual
2. Frost
3. Storm
4. Rain
5. External Input
6. Crop Protection
7. Fan&Pad
8. None