# Parameter Explanation Unit/Range Default
the settings defined for the higher
priority, which is Energy.
Note: Cannot set this parameter if the
Screen Functionality is set to Shading
8.
Temperature
dead band
The dead band of the temperature set
points
0
o
to +50
o
C 1
9.
Radiation limit
above
For Shading screen: above this set
radiation, the screen is spread
0 - 2500
W/m
2
1000
10.
Radiation limit
below
For energy screen: below this set
radiation and together with other
conditions, the screen is spread
0 - 2500
W/m
2
5
11.
Radiation dead
band
The dead band of the radiation set
points
0 - 2500
W/m
2
50
12.
Spread when
heating is on
Define if the screen will be spread
when the Heating system is active
NOTE: Relevant ONLY with the Energy
Screen
Yes/No No
Calculated / Status
13.
Condition Valid
Informs if all defined triggers are met
for activation of screen spreading
NOTE:
Shading = only 1 trigger needs to be
met in order to activate spread
Energy = ALL triggers must be met for
activation of spread
Yes/No
14.
Calculated
Screen Pos. %
Displays the screens target position
0 - 100 %
15.
Screen
Limitation
Screen function may be limited due to
a higher priority event
Ex: If it is snowing, then the screens
will proceed to the “SNOW” position,
and the Screen Limitation will display
Snow
1.
Storm
2. Snow
3. Manual
4. External Input
5. Crop Protection
6. Fan&Pad
7. Light