Doc. Name: NMC-PRO ׀ User Guide Ver 3.05.03 Revision: 2.2 Page: 46
Crop Management Technologies
# Parameter Explanation Unit/Range Default
9.
Release for
Temperature
NO: The use of the heater is only for CO2
YES: The use of the heater is for both
Heating and CO2
Yes/No Yes
10.
Dead band ON
Dead band in reference to the heating
temp (below). When the measured temp
in the zone is less than the 'heating temp'-
'dead band ON' value, the heater is ON
-50° to
+50
o
C
0.5
11.
Dead band OFF
Dead band in reference to the heating
temp (above). When the measured temp
in the zone is higher than the 'heating
temp'+'dead band OFF' the heater is OFF
-50° to
+50
o
C
0.5
12.
Release for
Humidity
Option to use the heater in order to
release the humidity in the zone
Yes/No Yes
13.
Humidity On %
If the measured humidity is above this set
point, the heater will be turned ON(can be
edited only when Release for Humidity is
set to “Yes”)
0 - 100% 0
14.
Humidity dead
band %
If the measured humidity is below the
“’Humidity On %’ minus 'Humidity Dead
Band %’”, the heater turns OFF (enabled
only when Release for Humidity is set to
”Yes”)
*See graph below “Example: Humidity
dead band for Heating”
0 - 100% 0
Calculated / Status
15.
Green House
Calculated
temperature
Displays the target temperature for the
green house with the settings and
influences taking into consideration
0° to +100° C
16.
Calculated
ON/OFF Heating
temperature
Displays the target temperature for the
ON/OFF heating system
0° to +100° C
17.
Limitation
Heating system may be limited due to a
higher priority event.
Ex: If Air Circulation is operating, then the
heating system will proceed to the “Air
Circulation” position, and the Heating
Limitation will display Air Circ.
1. Manual
2. External input
3. Air Circulation
4. None