Doc. Name: NMC-PRO ׀ User Guide Ver 3.05.03 Revision: 2.2 Page: 64
Crop Management Technologies
IMPORTANT: Verify that the SETUP parameters have been
defined and the Fan&Pad Inlet Calibrated!
# Parameter Explanation Unit/Range Default
1.
Period
It is possible to divide the day up to
6 periods. You can decide if the
period is On/Off.
1-6
2.
Active
Updated by the controller
(For indication only)
Yes/No Yes
3.
Start Time
Start Time for the period. The End
Time is signified by the Start Time
of the following period.
hh:mm --:--
4.
Temperature limit °C
If the temperature inside the
greenhouse is higher than the
Temp limit, then the Fan&Pad will
activate.
° C 26.0
5.
Release pad pump
Decide whether to use the pad
pump within the specified period.
Release = Yes use pad pump
Yes/No Yes
6.
Max fan stage
The maximum number of fan
stages that can be operating per
period.
1-8 8
7.
Release for Humidity
Option to release the fan stage for
humidity treatment.
There are 3 modes of operation –
Timer, Triggers or Timer&Triggers
1- None
2- Timer
3- Trigger
4- Timer&Trigger
None
1.5 Fan_Pad Prg. Zone 1 19/01/09 16:21
1. Period
2. Active
3. Start hh:mm
4. Temp limit °C
5. Release Pad Pump
6. Max fan stage
On
No
10:00
27.0
No
5
On
Yes
14:00
30.0
No
4
Off
No
Fan Stage Period
12. Fan stage #
13. Rel. fan stage
14. Fan stage on °C
1
Yes
26.0
2
Yes
28.0
3
Yes
27.0
Calculation/Status