# Parameter Explanation Unit/Range Default
8.
Difference Between
Inside and Outside
Humidity
The system checks the difference
between the inside humidity and
outside. If the difference is higher
than the set point, the humidity
release process begins.
This parameter exists only when
Trigger or Trigger+Timer mode are
selected.
-100% to +100% 100
9.
Minimum Outside
Temperature for
Humidity Release
Fan operation stops when the
outside temperature is below this
set point.
This line exists only when Release
for Hum is set to Yes.
0° to +50° C 28.0
10.
Timer Off time
The OFF/ON time of the fan stage
for humidity release.
Parameter exists only if Timer or
Trigger+Timer mode are selected.
mm:ss 00:00
11.
Timer On time mm:ss 00:00
Fan Stage
(settings should be considered for operating each period)
12.
Fan stage #
There are up to eight fan stages per
zone available
1-8
13.
Release Fan Stage
Option to permit the fan stage
Yes/No Yes
14.
Fan Stage temp On
The temperature set points to
start/stop the fan stage, when
Fan&Pad is activated.
0° to +50° C 26.0
15.
Fan Stage temp Off 0° to +50° C 24.0
16.
Humidity limit
Humidity release process stops
when the humidity is above this set
point.
These two parameters are
displayed only when Release for
hum is set to one of the 3 modes.
0-100 % 90
17.
Humidity dead band 0-20 % 10
Calculation / Status
18.
Temp F&P active
Displays the temperature that will
activate the Fan&Pad
0° to +50° C
19.
No. of fans active
Displays the number of fans that
are currently active.
0-8
20.
Pad pump active
Status of pad pump activity
Yes/No