NMC-PRO
USER GUIDE
Doc. Name: NMC-PRO ׀ User Guide Ver 3.05.03 Revision: 2.2 Page: 76
Crop Management Technologies
# Parameter Explanation Unit/Range Default
6.
Temp Limit
Define the temperature set point
and the direction above/below to
start air circulation.
NOTE: Press ENTER to edit, then use
+/- button to adjust arrow
direction, press ENTER and
use the number keypad to
define the limit, press ENTER
again to exit the parameter.
0° to +50° C 25.0
7.
Temp Dead band
Define the temp dead band for
ceasing operation of the air
circulation system.
0° to +50° C 3.0
8.
Humidity limit
Define the Humidity set point
and the direction above/below to
start air circulation
NOTE: Press ENTER to edit, then use
+/- button to adjust arrow
direction, press ENTER and
use the number keypad to
define the limit, press ENTER
again to exit the parameter.
0 - 100% 70
9.
Humidity dead band
Humidity Dead band for air
circulation system operation.
0 - 100% 5
10.
Temp diff limit
Define the temperature
difference between two or more
measuring boxes and the
direction above/below to start air
circulation
NOTE: Press ENTER to edit, then use
+/- button to adjust arrow
direction, press ENTER and
use the number keypad to
define the limit, press ENTER
again to exit the parameter.
0 - 50
o
C 3.0
11.
Temp diff dead band
Temperature difference dead
band for air circulation system
operation.
0 - 50
o
C 1.0
12.
Humidity diff limit
Define the Humidity difference
between two or more measuring
boxes and the direction
above/below to start air
circulation
NOTE: Press ENTER to edit, then use
+/- button to adjust arrow
direction, press ENTER and
0 - 100% 20