Doc. Name: NMC-PRO ׀ User Guide Ver 3.05.03 Revision: 2.2 Page: 82
Crop Management Technologies
IMPORTANT: Verify that the SETUP parameters have been
defined and the CO
2
Sensor/s calibrated!
# Parameter Explanation Unit/Range Default
1.
Period
It is possible to divide the day up to 6
periods. You can decide if the period is
On/Off.
ON/OFF ON
2.
Active
Updated by the controller
(For indication only)
Yes/No Yes
3.
CO
2
Mode
Passive – Only when heating source is
already working for heating then the
CO
2
operation will take place, but if
heating is not working then the CO
2
will remain off.
Active – In all cases of CO
2
demand it will
activate the CO
2
transport and valves
Liquid – The system opens the valve of a
tank containing liquid CO
2
for CO
2
enrichment
Passive
Active
Liquid
Act.
4.
Start Time
Start/Stop Time of the period.
hh:mm --:--
5.
End Time
6.
CO
2
concentration
The desired level of CO
2
in the Zone.
ppm 0
7.
Dead band OFF
The controller stops the CO
2
process when
it is above the desired concentration plus
the Dead band OFF parameter.
ppm 100
1. Period
2. Active
3. CO2 mode
4. Start hh:mm
5. End hh:mm
6. CO2 concent. Ppm
7.
Dead band off ppm
On
No
Pass.
05:30
11:45
700
50
On
Yes
Act.
14:00
16:00
950
50
Off
12. Calc. CO2 concentration ppm
13. Limitation
750
None