The following figure shows the back of a DE460C shelf with two fan canisters:
Attention: Possible equipment damage — If you replace a fan canister with the power turned on,
you must complete the replacement procedure within 30 minutes to prevent the possibility of
overheating the equipment.
Requirements for replacing a power supply
If you plan to replace a power supply, keep the following requirements in mind.
You must have a replacement power supply (power-fan canister) that is supported for your
controller shelf or drive shelf model.
You have an ESD wristband, or you have taken other antistatic precautions.
You can replace a power supply (power-fan canister) while your storage array is powered on and
performing host I/O operations, as long as the following conditions are true:
The second power supply (power-fan canister) in the shelf has an Optimal status.
The OK to remove field in the Details area of the Recovery Guru in SANtricity System
Manager displays Yes, indicating that it is safe to remove this component.
Attention: If the second power supply (power-fan canister) in the shelf does not have
Optimal status or if the Recovery Guru indicates that it is not OK to remove the power-fan
canister, contact technical support.