Requirements for replacing a power canister
If you plan to replace a power canister, keep the following requirements in mind.
You have a replacement power canister that is supported for your controller shelf or drive shelf
model.
You have one power canister that is installed and running.
You have an ESD wristband, or you have taken other antistatic precautions.
You can replace a power canister while your storage array is powered on and performing host I/O
operations, as long as the following conditions are true:
The other power canister in the shelf has Optimal status.
Note: While you perform the procedure, the other power canister supplies power to both
fans to ensure that the equipment does not overheat.
The OK to remove field in the Details area of the Recovery Guru in SANtricity System
Manager displays Yes, indicating that it is safe to remove this component.
Attention: If the second power canister in the shelf does not have Optimal status or if the
Recovery Guru indicates that it is not OK to remove the power canister, contact technical
support.
Requirements for replacing a fan canister
If you plan to replace a fan canister, keep the following requirements in mind.
You have a replacement fan canister (fan) that is supported for your controller shelf or drive shelf
model.
You have one fan canister that is installed and running.
You have an ESD wristband, or you have taken other antistatic precautions.
If you perform this procedure with the power turned on, you must complete it within 30 minutes
to prevent the possibility of overheating the equipment.
You can replace a fan canister while your storage array is powered on and performing host I/O
operations, as long as the following conditions are true:
The second fan canister in the shelf has an Optimal status.
The OK to remove field in the Details area of the Recovery Guru in SANtricity System
Manager displays Yes, indicating that it is safe to remove this component.
Attention: If the second fan canister in the shelf does not have Optimal status or if the
Recovery Guru indicates that it is not OK to remove the fan canister, contact technical
support.
Replace power supply (24-drive)
Each 24-drive controller shelf or drive shelf includes two power supplies with integrated fans. These
are referred to as
power-fan canisters
in SANtricity System Manager. If a power-fan canister fails,
you must replace it as soon as possible to ensure that the shelf has a redundant power source and
adequate cooling.
Canisters |
37