14-6
14.2.2.4. Control AC Line Under-Voltage
[Output] DRDY: Open
[TA] P3 > Control AC Line Under Voltage
[LED] P3
[Motor Condition] Servo-OFF
Table 14-6: Cause and Remedy: Control AC line under-voltage
Cause Remedy
(1) Low voltage of control power input. Check control power voltage.
(Low voltage due to over current or output shorting.)
(2) Control circuit voltage for the power amplifier
falls below 70V due to faulty power supply.
Turn off power, check the power supply and power
cable, then turn on power again.
(3) Faulty PCB.
(When the alarm is on after control power is
turned on.)
Replace Driver Unit.