15-3
15.2.1. Power Trouble
Power is not turned on.
Figure 15-2 : Power trouble
NO
NO
YES
YES
OK
Check the terminal block of the front panel of Driver Unit
for main power and control power with a tester, etc.
Turn on power.
Connect Handy Terminal.
Communication enable?
Replace Driver Unit.
Both control power and
main power supplied?
Power is not turned on.