EasyManuals Logo

Omron 3G3JX User Manual

Omron 3G3JX
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #127 background imageLoading...
Page #127 background image
4-42
4-2 Function Mode
4
Functions
Overcurrent Suppression Function
This function suppresses overcurrent caused by a steep current rise in rapid acceleration.
Select to enable or disable the overcurrent suppression function in b140.
This function does not operate during deceleration.
Automatic Carrier Frequency Reduction Function
This function automatically lowers the set carrier frequency when the temperature of the
semiconductor inside the Inverter becomes high.
While this function is activated, the noise from the motor may be heard differently because of
automatic change in career frequency.
RDY (Ready) Function
This function prepares for Inverter output to rotate the motor immediately after a RUN command is
input. When this function is enabled and the RDY signal is sent to the multi-function input terminal,
high voltage is applied to terminals U, V, and W on the main circuit terminal block. This happens
even if the motor is stopped with the RUN command turned off. Do not touch the main circuit
terminal block.
Parameter No. Function name Data Default setting Unit
b140
Overcurrent suppression
function
00: Disabled
01: Enabled
01
Output
frequency
Desired
Actual acceleration after
suppression operation
Time
Output
current
Time
Suppression level
(about 160% of the rating)
Parameter No. Function name Data Default setting Unit
b150
Automatic carrier
reduction
00: Disabled
01: Enabled
00
Parameter No. Function name Data Default setting Unit
b151 Ready function selection
00: Disabled
01: Enabled
00

Table of Contents

Other manuals for Omron 3G3JX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3JX and is the answer not in the manual?

Omron 3G3JX Specifications

General IconGeneral
Model3G3JX
CategoryInverter
Control MethodV/f control
Input Frequency50/60 Hz
Communication InterfaceRS-485 (optional)
Operating Temperature-10 to 50°C
Humidity20 to 90% RH (non-condensing)
Enclosure RatingIP20
Input Voltage200 to 240 V AC
Output VoltageThree-phase 200 to 240 V AC
Output Frequency400 Hz
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Braking UnitBuilt-in
Power Range0.1 to 15 kW
Cooling MethodFan-cooled
Storage Temperature-20°C to +65°C
AltitudeUp to 1000 m

Related product manuals