EasyManua.ls Logo

Omron 3G3JX

Omron 3G3JX
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-21
4-2 Function Mode
4
Functions
Target Value Selection
The target value depends on the terminal selected in frequency reference A001 other than that in
A076.
You cannot set analog inputs FV and FI to both target and feedback values simultaneously. Do not
connect the signal lines for inputs FV and FI simultaneously.
Feedback Selection
Select a terminal for feedback signals in A076.
The setting of FV/FI terminal selection A005 is disabled when the control terminal block (terminal)
01 is set in A001.
PID Feedback Value Monitor
You can monitor the PID feedback value in d004.
The monitor value is displayed as the multiplied value of the PID scale (A075).
Monitor display = Feedback value (%) × A075 setting
Excessive Deviation/Output
You can set the PID deviation excessive level (C044) during PID control. If the PID deviation
reaches the PID deviation excessive level (C044), the multi-function output terminal is turned on.
C044 can be set from 0 to 100. The setting corresponds to the range of 0 to the maximum target
value.
Allocate 04 (OD) to any of the multi-function output terminal P1 selection (C021) or relay output
(MA, MB) function selection (C026).
PID Feedback (FB) Upper/Lower Limit
If the feedback value exceeds the upper limit set in C052, FBV, which is allocated to the multi-
function output terminal, turns on. If the value falls below the lower limit set in C053, FBV turns off.
PID Operation
P Operation
Operation where the control volume is proportional to the target value
I Operation
Operation where the control volume increases linearly according to time
Small
Target value
Control volume
Step transition
Large
A072
Ramp transition
Small
Large
A072
Large
Small
Target value
Control volume
A073
Large
Small
A073

Table of Contents

Other manuals for Omron 3G3JX

Related product manuals