4-23
4-2 Function Mode
4
Functions
AVR Function
This function outputs voltage to the motor correctly even if the incoming voltage to the Inverter
fluctuates. With this function, output voltage to the motor is based on that set in the AVR voltage
selection.
With A081 (AVR selection), set whether to enable or disable this function.
Note that the Inverter cannot output voltage beyond that of the incoming voltage.
To avoid a possible overcurrent trip during deceleration, set the AVR selection to "Always ON"
(A081: 00).
Automatic Energy-saving Operation Function
This function automatically adjusts the Inverter output power to a minimum during constant speed
operation. This is suitable for the load of reduced torque characteristics, such as a fan and pump.
To operate with this function, set the RUN mode selection (A085) to 01. You can adjust the
response and accuracy in the energy-saving response/accuracy adjustment (A086).
Controls the output power at a comparatively slow rate. Should rapid load fluctuation like impact
load occur, the motor may stall, resulting in an overcurrent trip.
Parameter No. Function name Data Default setting Unit
A081 AVR selection
00: Always ON
01: Always OFF
02: OFF during deceleration
02
A082
AVR voltage
selection
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
200/400
Related functions d004, A001, A005
Parameter No. Data Description Note
A081
00 Always ON
Enabled during acceleration, constant speed operation, and
deceleration.
01 Always OFF
Disabled during acceleration, constant speed operation, and
deceleration.
02
OFF during
deceleration
Disabled only during deceleration in order to reduce the energy
regenerated to the Inverter by increasing the motor loss. This will
avoid a possible trip due to regeneration during deceleration.
Parameter No. Function name Data Default setting Unit
A085 RUN mode selection
00: Normal operation
01: Energy-saving operation
00
A086
Energy-saving response/
accuracy adjustment
0 to 100% 50 %
Parameter No. Data Response Accuracy Energy-saving effect
A086
0
100
Slow
Fast
High
Low
Small
Large

Table of Contents