The following describes the wiring for the main power supply input terminals and for peripheral equip- 
ment. 
 
⚫
 
Installing molded case circuit breaker 
If the inverter’s protective function is activated, the inverter internal circuit may be damaged depend- 
ing on the condition. 
Be sure to connect the main power supply input terminals (R/L1, S/L2, T/L3) to the power supply via 
a molded case circuit breaker (MCCB) according to each inverter. 
• 
When using multiple inverters, install one MCCB per inverter. 
• 
Determine the capacity of the MCCB according to the molded case circuit breaker (MCCB) value 
shown in the previous table. 
• 
Determine the time characteristic of the MCCB upon due consideration of the time characteristic 
of the inverter’s overheat protection function (150% of the rated output current for 1 minute). 
• 
If you must share one MCCB with multiple inverters or other equipment, construct a sequence 
that turns OFF the power supply via the alarm output signal, as shown in the figure below. 
Inverter 
 
 
 
 
 
3-phase 200 
3-phase 400 
 
 
 
 
 
 
 
 
*1.  For 400-V class, connect a 400/200-V transformer. 
*2.  Set the Multi-function Relay Output (AL1, AL2) Function Selection (C026) to 05 (AL: Alarm signal). 
*3.  Set the Multi-function Relay Output (AL1, AL2) Operation Selection (C036) to 00 (NO: NO contact) to 
configure the terminal AL2 as NC contact.