Loading...
5 Basic Settings
5 - 51
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Data
Default data
Unit
C001 to
C007
Multi-function Input 1 to 7
Selection
06: JG (Jogging)
A038
Jogging Frequency
0.00
Starting Frequency to 10.00 (100.00)
*1
6.00
Hz
A039
Jogging Stop Selection
00: Free-running on jogging stop/Dis-
abled during operation
01: Deceleration stop on jogging
stop/Disabled during operation
02: DC injection braking on jogging
stop
*2
/Disabled during operation
03: Free-running on jogging
stop/Enabled during operation
04: Deceleration stop on jogging
stop/Enabled during operation
05: DC injection braking on jogging
stop
*2
/Enabled during operation
04
5
5-9 Multi-function Input Settings