5 Basic Settings
5 - 62
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Data
Default data
Unit
b130
Overvoltage Suppression Func-
tion Selection During Deceleration
00: Disabled
01: Enabled (DC voltage kept
constant) (Example 1)
*1
02: Enabled (Acceleration
enabled) (Example 2)
01
b131
Overvoltage Suppression Level Dur-
ing Deceleration
*2
200-V class: 330. to 400.
400-V class: 660. to 800.
380./760.
V
b132
Overvoltage Suppression Parame-
ter During Deceleration
0.10 to 30.00:
Set the acceleration rate for the
output frequency when the over-
voltage suppression during
deceleration function is enabled.
Set the acceleration time from 0
Hz to the maximum frequency.
1.00
s
b133
Overvoltage Suppression Propor-
tional Gain During Deceleration
0.00 to 5.00:
Proportional gain for DC voltage
constant control (b130 = 01 only)
0.20
b134
Overvoltage Suppression Integral
Time During Deceleration
0.0 to 150.0:
Integral time when DC voltage is
kept constant (b130 = 01 only)
1.0
s
b090
Usage Rate of Regenerative Brak-
ing
0.0:
Regenerative braking not
active
0.0
%
b095
Regenerative Braking Selection
00: Disabled
0.0