7 Other Functions
7 - 44
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Data
Default
data
Unit
A071
PID Selection
00: Disabled
01: Enabled
02: Enabled (Reverse output enabled)
00
A072
PID P Gain
0.00 to 25.00
Set the proportional gain
1.00
A073
PID I Gain
0.0 to 3600.0
Set the integral time
1.0
s
A074
PID D Gain
0.00 to 100.00
Set the derivative time
0.00
s
A075
PID Scale
0.01 to 99.99
For unit conversion for PID Feedback
Value Monitor (d004)
1.00
time
A076
PID Feedback Selection
00:
Analog current (Terminal OI)
*1
4 to 20 mA
01:
Analog voltage (Terminal O)
*1
0 to 10 V
02: Modbus communication
03: Pulse train frequency
10:
Operation function output
*1
00
A077
PID Deviation Reverse
Output
00: Disabled (Deviation = Target value
Feedback value)
01: Enabled (Deviation = Feedback
value Target value)
00
A078
PID Variable Range Limit
0.0 to 100.0
Variable range based on target value
0.0
%
A079
PID Feedforward
Selection
00: Disabled
01:
Analog voltage (Terminal O)
*2
0 to 10 V
02:
Analog current (Terminal OI)
*3
4 to 20 mA
00
A156
PID Sleep Operation
Level
0.00 to 590.00
Stops inverter operation if PID output is at
the operation level or lower.
0.00
Hz