7 Other Functions
7 - 27
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function
name
Data
Description
PWM/
Pulse
Full-scale value
C027
EO
Selection
00
Output frequency
*1 *2
PWM
0 to Maximum frequency [Hz]
01
Output current
PWM
0 to 200%
02
Output torque
*3
PWM
0 to 200%
03
Digital output frequency
*4
Pulse
0 to Maximum frequency [Hz]
04
Output voltage
PWM
0 to 133%
(Example: For 200-V class, 7.5 V
at 200 V)
05
Input power
PWM
0 to 200%
06
Electronic thermal load rate
PWM
0 to 100%
07
LAD frequency
*1
PWM
0 to Maximum frequency [Hz]
08
Digital current monitor
Pulse
Refer to EO Gain Setting on page
7-28.
10
Cooling fin temperature
PWM
0 to 200°C (Outputs 0°C for 0°C or
lower)
12
DriveProgramming (YA(0))
PWM
Use DriveProgramming to set this
function. (0.00 to 100.00%)
15
Pulse train input monitor
Pulse
Refer to EO Gain Setting on page
7-28.
16
Option (No applicable
Option)
7
7-3 Analog I/O Settings
7-3-6 Terminal EO (Pulse/PWM Output)
EO Selection

Table of Contents

Related product manuals