7 Other Functions
7 - 65
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Data
Description
Default
data
Unit
b001
Power Interruption/Under-
voltage Restart Selection
*1 *2
00
Trip
00
−
01
0-Hz restart
02
Frequency pull-in restart at shutoff
*3
03
Frequency pull-in restart (Trip after
deceleration stop)
*3 *4
04
Frequency pull-in restart
b002
Allowable Power Interrup-
tion Time
0.3 to 25.0
The inverter restarts if the power
interruption duration is shorter than
the set time. (Example 1)
The inverter trips if the power inter-
ruption duration is equal to or longer
than the set time. (Example 2)
1.0
s
b003
Restart Standby Time
0.3 to 100.0
Set the wait time until the inverter
restarts.
1.0
s
b004
Power Interruption/Under-
voltage Trip Selection Dur-
ing Stop
*1
00
Disabled (Trip disabled during stop)
00
−
01
Enabled (Trip also enabled during
stop)
02
Disabled during stop and during
deceleration by RUN command
OFF.
b005
Power Interruption Restart
Count
00
16 times
00
−
01
No limit
7-7-2 Restart during Power Interruption, Undervoltage/Overvoltage,
Overcurrent
Restart during Power Interruption, Undervoltage/Overvoltage,
Overcurrent