Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1) 
 
 
 
 
 
 
 
7-6-10  User Parameter Setting Function   
 
The parameter group U consists of user parameters. Up to 32 user parameters can be registered as 
desired. When registration is done, set the Display Selection (b037) to 02 (User setting). After that, you 
will see only the functions registered with U001 to U032 in addition to d001, F001, b037, b190 and 
b191. 
 
no:  No registration 
d001 to P196 
Register any parameter. 
02:  User setting + d001, F001, b037 
 
 
7-6-11  User Parameter Automatic Setting Function   
 
When the User Parameter Automatic Setting Function (b039) is set to 01 (Enabled), the parameters 
with changed data are stored automatically in an ascending order from U001 to U032. This function is 
useful as the change history. 
The data (parameter setting) displayed on the screen is stored at the time when you press the Enter 
key. This is also applicable for storing the monitor functions (d***). 
U001 stores the most recent parameter data; U032 stores the oldest. 
If the same parameter was changed, the previous change is deleted and the last one is stored. In addi- 
tion, if the number of the parameters exceeds 32, the data is deleted from the oldest (U032). 
 
User Parameter Automatic Setting 
Function 
Note Be aware that changing the 039 value from 00 to 01 initializes (resets to “no”) all parameter data registered 
to the user parameters U001 to U032.