8 Communications Functions
8 - 41
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec.
No
Function name
Parameter No.
R/W
Monitor or setting
data
Data
resolution
0000
hex
Reserved
0001
hex
0000 hex
Output Frequency
Setting/Monitor
F001 (HIGH)
R/W
0 to 59000
(Enabled when
A001 = 03)
0.01
[Hz]
*1
0002
hex
0001 hex
F001 (LOW)
R/W
0003
hex
0002 hex
Inverter Status A
R
0: Initial status
2: Stop
3: Run
4: Free-run stop
5: Jogging
6: DC injection
braking
8: Trip
9: During UV
0004
hex
0003 hex
Inverter Status B
R
0: During stop
1: During RUN
2: During trip
0005
hex
0004 hex
Inverter Status C
R
0:
1: Stop
2: Deceleration
3: Constant
speed
4: Acceleration
5: Forward
6: Reverse
7: Forward to
reverse
8: Reverse to
forward
9: Forward run
start
10: Reverse run
start
8
8-9 Modbus Communication Data Lists
8-9-2 Monitor Function/Enter Command Regis-
ter List