4 Parameter List
4 - 14
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Changes
during
RUN
Unit
Page
Momentary
power
interruption/Trip
restart
b001
Power Interruption/
Undervoltage Restart
Selection
00: Trip
01: 0-Hz restart
02: Frequency pull-in restart at shutoff
03: Trip after frequency pull-in deceler-
ation stop
04: Frequency pull-in restart
00
Enabled
−
P. 7-62
b002
Allowable Power
Interruption Time
0.3 to 25.0
1.0
Enabled
s
b003
Restart Standby Time
0.3 to 100.0
1.0
Enabled
s
b004
Power Interruption/
Undervoltage Trip
Selection During Stop
00: Disabled
01: Enabled
02: Disabled during stop and decelera-
tion stop by turning off the RUN
command
00
Enabled
−
b005
Power Interruption
Restart Count
00: 16 times
01: No limit
00
Enabled
−
b007
Trip
after
frequency
pull-in
deceleration
stop
0.00 to 590.00
0.00
Enabled
Hz
b008
Overvoltage/
Overcurrent Restart
Selection
00: Trip
01: 0-Hz restart
02: Frequency pull-in restart at shutoff
03: Trip after frequency pull-in deceler-
ation stop
04: Frequency pull-in restart
00
Enabled
−
b010
Overvoltage/
Overcurrent Restart
Count
1 to 3
3
Enabled
time
b011
Overvoltage/
Overcurrent Restart
Standby Time
0.3 to 100.0
1.0
Enabled
s