7 Other Functions
7 - 70
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Data
Default
data
Unit
b050
Deceleration Stop Selec-
tion on Power Interrup-
tion
00: Disabled
01: Enabled (Deceleration stop)
02: Enabled (Constant voltage, without recovery)
*1
03: Enabled (Constant voltage, with recovery)
00
−
b051
Starting Voltage on
Power Interruption
*2
200-V class: 0.0 to 400.0
400-V class: 0.0 to 800.0
The function will be activated if the main circuit DC
voltage drops to the set value or lower.
200-V
class:
220.0
400-V
class:
440.0
V
b052
Deceleration Hold Level
on Power
Interruption
*2*3
200-V class: 0.0 to 400.0
400-V class: 0.0 to 800.0
The inverter will stop decelerating if the voltage rise
caused by regeneration exceeds the set value after
starting operation.
200-V
class:
360.0
400-V
class:
720.0
V
b053
Deceleration Time on
Power Interruption
*4
0.01 to 3600.00
Set the deceleration time for the deceleration stop on
power interruption function.
1.00
s
b054
Deceleration Starting
Width on Power
Interruption
*4
0.00 to 10.00 (100.00)
*5
Set when you want to have the inverter start deceler-
ating as the difference from the output frequency.
0.00
Hz
b133
Overvoltage Suppression
Proportional Gain During
Deceleration
0.00 to 5.00
0.20
−
b134
Overvoltage Suppression
Integral Time During
Deceleration
0.0 to 150.0
1.0
s
Related functions
b001
7
7-7 Restart Functions
7-7-4 Deceleration Stop on Power Interruption Function