7 Other Functions
7 - 42
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Data
Default
data
Unit
A081/A281
1st/2nd AVR Selection
00: Always ON
01: Always OFF
02:
OFF during deceleration
*1
02
A082/A282
1st/2nd Motor Rated Volt-
age Selection
200 V: 200 to 240
400 V: 380 to 480
200 or 400
V
Parameter
No.
Function name
Data
Default
data
Unit
b130
Overvoltage Suppression
Function Selection During
Deceleration
00: Disabled
01
A081/A281
1st/2nd AVR Selection
00: Always ON
02
A082/A282
1st/2nd Motor Rated Volt-
age Selection
200 V: 200 to 240
400 V: 380 to 480
200 or 400
V
A083
AVR Filter Time Constant
0.000 to 10.000
0.300
s
A084
AVR Gain at Deceleration
50. to 200.
100.
%
AVR (Automatic Voltage Regulator) Function Settings