Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
The main parameters related to frequency pull-in restart are as follows.
For details on free-run stop, refer to 5-7-2 Free-run Stop Selection on page 5-38.
0.3 to 100.0
Set the wait time until the inverter restarts.
Frequency Pull-in Lower
Limit Frequency
0.00 to 590.00
Executing the function causes the Inverter to
restart from 0 Hz if the frequency at shutoff is
the set value of b007 or less.
Frequency Pull-in Restart
Level
0.20 ï‚´ Rated current to 2.00 ï‚´ Rated current
Rated
current of
inverter
Frequency Pull-in Restart
Parameter
0.1 to 3000.0
Set the deceleration rate for the output fre-
quency during frequency pull-in restart.
Set the deceleration time from the maximum
frequency to 0 Hz.
Starting Frequency Selec-
tion at Frequency Pull-in
Restart
00: Frequency at shutoff
01: Maximum frequency
02: Set frequency (Frequency reference)
7-7-1 Frequency Pull-in Restart