4 Parameter List
4 - 8
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Changes
during
RUN
Unit
Page
Multi-step speed,
jogging
A019
Multi-step Speed
Selection
00: Binary (16-step selection with 4 ter-
minals)
01: Bit (8-step selection with 7 termi-
nals)
00
Disabled
P. 5-48
A020
1st Multi-step Speed
Reference 0
0.00
Starting Frequency to 1st Maximum Fre-
quency
6.00
Enabled
Hz
A220
2nd Multi-step Speed
Reference 0
0.00
Starting Frequency to 2nd Maximum Fre-
quency
6.00
Enabled
Hz
A021
Multi-step Speed
Reference 1
0.00
Starting Frequency to
Maximum Frequency
0.00
Enabled
Hz
A022
Multi-step Speed
Reference 2
A023
Multi-step Speed
Reference 3
A024
Multi-step Speed
Reference 4
A025
Multi-step Speed
Reference 5
A026
Multi-step Speed
Reference 6
A027
Multi-step Speed
Reference 7
A028
Multi-step Speed
Reference 8
A029
Multi-step Speed
Reference 9
A030
Multi-step Speed
Reference 10
A031
Multi-step Speed
Reference 11
A032
Multi-step Speed
Reference 12
A033
Multi-step Speed
Reference 13
A034
Multi-step Speed
Reference 14
A035
Multi-step Speed
Reference 15
A038
Jogging Frequency
Starting Frequency to 10.00 (100.00)
*1
6.00
Enabled
Hz
P. 5-51
A039
Jogging Stop Selec-
tion
00: Free-running on jogging stop/Dis-
abled during operation
01: Deceleration stop on jogging stop/
Disabled during operation
02:
DC injection braking on jogging stop/
Disabled during operation
03: Free-running on jogging stop/
Enabled during operation
04: Deceleration stop on jogging stop/
Enabled during operation
05:
DC injection braking on jogging stop/
Enabled during operation
04
Enabled