4 Parameter List
4 - 23
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Changes
during
RUN
Unit
Page
Auxiliary
function
b145
GS Input Operation
Selection
00: No trip (shut off by hardware)
01: Trip
00
Enabled
−
P. 7-
103
b150
Inverter Display on
Operator Connection
001 to 060
(Corresponding to d001 to d060)
001
Enabled
−
P. 7-57
b160
User Monitor Selection
1
001 to 030
(Corresponding to d001 to d030)
001
Enabled
−
P. 7-13
b161
User Monitor Selection
2
001 to 030
(Corresponding to d001 to d030)
002
Enabled
−
b163
d001/d007 Data Set-
ting Selection
00: Disabled
01: Enabled
00
Enabled
−
P. 7-4
P. 7-6
b164
Initial Screen Auto-
matic Return Function
00: Disabled
01: Enabled
00
Enabled
−
P. 7-56
b165
Operation Selection
at External Operator
Disconnection
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free-run stop
04: Deceleration stop
02
Enabled
−
P. 7-56
b166
(Reserved)
Do not change the default 00.
00
−
−
−
Mode
b171
Inverter Mode Selec-
tion
00: Selection disabled
01: Induction motor mode
02:
Induction motor high-frequency
mode
03: PM motor mode
00
Disabled
−
P. 6-58
Auxiliary
function
b180
Initialization Execu-
tion
00: Function disabled
01: Execute initialization
00
Disabled
−
P. 5-5
b190
Password A Setting
0000: Function disabled
0001 to FFFF: Password
0000
Disabled
−
P. 7-57
b191
Password A for
Authentication
0000 to FFFF
0000
Disabled
−
b192
Password B Setting
0000: Function disabled
0001 to FFFF: Password
0000
Disabled
−
b193
Password B for
Authentication
0000 to FFFF
0000
Disabled
−
Electronic
thermal
b910
Motor Electronic Ther-
mal Selection
00: Disabled
01: Enabled (Fixed subtraction ratio)
02:
Enabled (b911 subtraction ratio)
03: Enabled (b912 time parameter sub-
traction)
03
Enabled
−
P. 7-74
b911
Motor Electronic Ther-
mal Subtraction Ratio
0.10 to 100000.00
*1
(Displays upper 5 digits)
600.00
Enabled
s
b912
Motor
Electronic
Ther-
mal Subtraction Time
Constant
0.10 to 100000.00
*1
(Displays upper 5 digits)
120.00
Enabled
s
b913
Motor
Electronic
Ther-
mal
Integration
Gain
1.0 to 200.0
100.0
Enabled
%
b914
Electronic Thermal
Load Rate at Power-
off
*2
00: Disabled
01: Enabled
01
Enabled
−
4
4-3 Extended Function Mode
4-3-2 Group b: Detailed Function Parameters