Precautions for Correct Use 
• 
Check the maximum allowable current (limiting current beyond which demagnetization 
occurs) for your PM motor. 
The inverter could output approximately 300% of the rated output current of the inverter. 
Select a PM motor as follows to prevent demagnetization. 
When comparing each motor specification, note whether it is an effective value or a peak 
value. The inverter’s rated current is an effective value. 
Maximum current of PM motor > Approx. 300% of rated output current of inverter 
 
• 
In the PM motor mode, some of the inverter functions are unavailable. Unavailable parame- 
ters are not displayed on the Digital Operator. 
Refer to 6-8-2 Functional Limitations in PM Motor Mode on page 6-56. 
• 
The PM motor control mode is applied to one single motor. It is not possible to drive more 
than one PM motor with a single inverter. 
• 
With an extremely large load, this control may not keep the PM motor in a synchronized 
state. 
As a guide, the motor-shaft conversion of the moment of load inertia shall be not more than 
30 times as great as the moment of inertia of the PM motor.